Power Usage Effectiveness has become the industry’s favourite headline number, but it is also one of the most routinely misrepresented.

It is often quoted using design estimates rather than operational measurements, lifted from aged case studies that no longer reflect live load profiles, or derived from selective time periods that flatter performance. “Design PUE” is presented as if it were measured reality. Winter snapshots are described as annual performance. Partial calculations are compared with full-facility averages. By the time the figure reaches a board slide, it can be several steps removed from operational truth.

That is before we even consider what PUE actually measures.

Under ISO 30134-2 and EN 50600-4-2, PUE is defined as total facility energy divided by IT equipment energy. It is a building efficiency ratio. It tells you how much supporting energy the facility consumes in order to deliver power to the IT load. Cooling, power conversion losses and ancillary systems sit in the numerator. The IT load sits in the denominator.

When measured correctly, using annualised averages and properly defined metering boundaries, it is a useful engineering indicator. It highlights mechanical inefficiencies, distribution losses and control issues. It allows infrastructure teams to track whether containment improvements, plant upgrades or set point adjustments are having the intended effect.

The issue arises when PUE is treated as a proxy for sustainability performance rather than a measure of infrastructure proportionality. Because it is a ratio, PUE can improve simply by increasing IT load relative to fixed building overhead. Populate a hall with additional servers and, assuming infrastructure remains broadly constant, the denominator grows faster than the numerator. The PUE falls. On paper, efficiency improves. In practice, total electricity consumption has increased and so have associated emissions.

Equally, if you rationalise workloads, decommission legacy equipment and reduce overall IT demand, the building overhead becomes proportionally larger and PUE can deteriorate. Absolute consumption falls, yet the headline metric moves in the wrong direction.

That dynamic makes it unsuitable as a standalone sustainability signal. However, this is where nuance matters.

Partial PUE, measured at hall, zone or even rack level, is often dismissed in debates about “true” PUE. That is a mistake. While partial figures are not comparable to whole-site annualised PUE, they are operationally powerful. A hall-level PUE can expose:

  • Airflow imbalance between zones
  • Overcooling in lightly loaded areas
  • Inefficient legacy halls versus modernised space
  • The impact of high-density deployments on supporting infrastructure

Zone-level or rack-level PUE can help teams understand whether a specific containment strategy is working, whether temperature set points are appropriate, or whether certain IT categories are disproportionately driving cooling demand.

These insights shape real decisions, they inform workload placement within a facility. They influence whether high-density AI or GPU clusters are consolidated into optimised zones rather than spread across inefficient space. They support prioritisation of retrofit investment. They provide evidence for adjusting cooling strategies rather than simply lowering temperatures across the board.

In other words, partial PUE is a tactical efficiency tool. It helps operators manage intra-site efficiency and make better engineering decisions. What it does not do is replace the need for whole-facility annualised measurement, nor does it solve the broader question of environmental impact.

PUE, whether whole-site or partial, tells you nothing about server utilisation, application efficiency, workload necessity, grid carbon intensity, renewable coverage or water dependency. A fossil-heavy grid can deliver an excellent PUE. A water-intensive cooling design can do the same. The ratio cannot see those dimensions.

Meanwhile, regulatory and corporate expectations are moving towards recording detailed energy consumption, transparent Scope 1 and Scope 2 reporting, renewable sourcing disclosure and clarity over location-based carbon intensity. In that context, PUE becomes one indicator within a broader governance framework, not the defining measure of performance.

Used properly, it remains valuable. It should be measured accurately, annualised at site level, and instrumented intelligently at hall and zone level to drive operational improvement.

But it needs context. Data centres today underpin critical digital services and increasingly energy-intensive workloads. If we want credible environmental governance, the conversation has to extend beyond a single ratio and towards absolute demand, IT efficiency, renewable alignment and carbon intensity.

PUE tells you something about the building, at hall and zone level, it can help you run that building better. It does not, on its own, tell you whether the system is sustainable.